13.7.6 Pulse timer function block PULSETIMER
IP11016-1 v2
M11466-3 v3
The pulse (PULSETIMER) function can be used, for example, for pulse extensions
or limiting the operation time of outputs. The PULSETIMER has a settable length.
When the input is 1, the output will be 1 for the time set by the time delay
parameter t. Then it returns to 0.
13.7.6.1 Function block
M11465-3 v4
PULSETIMER
INPUT OUT
IEC04000407-3-en.vsd
IEC04000407 V3 EN-US
Figure 259: PULSETIMER function block
13.7.6.2 Signals
PID-6985-INPUTSIGNALS v1
Table 314: PULSETIMER Input signals
Name
Type Default Description
INPUT BOOLEAN 0 Input to pulse timer
PID-6985-OUTPUTSIGNALS v1
Table 315: PULSETIMER Output signals
Name
Type Description
OUT BOOLEAN Output from pulse timer
13.7.6.3 Settings
PID-6985-SETTINGS v1
Table 316: PULSETIMER Non group settings (basic)
Name
Values (Range) Unit Step Default Description
t 0.000 - 90000.000 s 0.001 0.010 Time delay of function
13.7.6.4 Technical data
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1
Table 317: Number of PULSETIMER instances
Logic block
Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms
1MRK 506 382-UEN A Section 13
Logic
Line distance protection REL650 2.2 IEC 497
Technical manual