17.4.6.4 Settings
SEMOD55954-1 v2
PID-6753-SETTINGS v1
Table 487: MVGAPC Non group settings (basic)
Name
Values (Range) Unit Step Default Description
BasePrefix micro
milli
unit
kilo
Mega
Giga
Tera
-
- unit Base prefix (multiplication factor)
MV db 1 - 100000 Type 1 10000 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 500 1000 Zero point clamping in 0,001% of range
MV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the base
prefix (multiplication factor)
MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix
(multiplication factor)
MV lLim -5000.00 - 5000.00 xBase 0.01 -800.00 Low limit multiplied with the base prefix
(multiplication factor)
MV llLim -5000.00 - 5000.00 xBase 0.01 -900.00 Low Low limit multiplied with the base
prefix (multiplication factor)
MV min -5000.00 - 5000.00 xBase 0.01 -1000.00 Minimum value multiplied with the base
prefix (multiplication factor)
MV max -5000.00 - 5000.00 xBase 0.01 1000.00 Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Deadband Reporting type
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
17.4.6.5 Monitored data
PID-6753-MONITOREDDATA v1
Table 488: MVGAPC Monitored data
Name
Type Values (Range) Unit Description
VALUE REAL - - Magnitude of deadband
value
RANGE INTEGER 1=High
2=Low
3=High-High
4=Low-Low
0=Normal
-
Range
Section 17 1MRK 506 382-UEN A
Station communication
678 Line distance protection REL650 2.2 IEC
Technical manual