-0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8
-0.4
-0.2
0
0.2
0.4
0.6
Real part (R) of Z in Ohms
Imaginary part (X) of Z in Ohms
R[Ohm]
no trip
region
loci of Z(R, X)
no trip
region
rotor angle
= ±180°
X[Ohm]
RE - Receiving End (infinite bus)
this circle
is loci of
the rotor
angle = 90°
2
relay
SE - Sending End (generator)
no trip
region
inside
circle
outside the
circle is the trip
region for
TripAngle <= 90°
3
here rotor
angle
is -90°
here
rotor angle
is +90°
1
trip
region
Z - line connects
points SE & RE
IEC10000114-1-en.vsd
IEC10000114 V1 EN-US
Figure 66: The imaginary offset Mho circle represents loci of the impedance
Z(R, X) for which the rotor angle is 90 degrees
0 200 400 600 800 1000 1200
-5
0
5
10
15
20
25
30
35
Current in kA, trip command to CB, rotor angle in rad
Time in milliseconds
pos. seq. current in kA
trip command to CB
rotor angle in radian
fault
occurs
normal load current
min. current
very high currents due
to out-of-step condition
after 1st
pole slip
2nd
rotor angle
angle towards
current decreases
fault cleared
current increases under
fault conditions
tBreaker = 60 ms
trip command
issued here
IEC10000115-1-en.vsd
IEC10000115 V1 EN-US
Figure 67: Trip initiation when the break-time of the circuit breaker is known
Section 6 1MRK 506 382-UEN A
Impedance protection
146 Line distance protection REL650 2.2 IEC
Technical manual