Name Values (Range) Unit Step Default Description
I2-2> 1 - 2500 %IB 1 50 Negative sequence current op level for
step 2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Time delay of step 2 when definite time
char. is selected
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 10000.00 %IB 1.00 50 Minimum current for step 2
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 2
DirMode3 Off
Non-directional
Forward
Reverse
-
- Non-directional Directional mode of step 3 (off, nodir,
forward, reverse)
Characterist3 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - ANSI Def. Time Time delay characteristic for step 3
I2-3> 1 - 2500 %IB 1 33 Negative sequence current op level for
step 3 in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Time delay of step 3 when definite time
char. is selected
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 10000.00 %IB 1.00 33 Minimum current for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse time
characteristic step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current setting
value for step 3
DirMode4 Off
Non-directional
Forward
Reverse
-
- Non-directional Directional mode of step 4 (off, nodir,
forward, reverse)
Table continues on next page
Section 7 1MRK 506 382-UEN A
Current protection
208 Line distance protection REL650 2.2 IEC