19.11 Primary system values PRIMVAL
19.11.1 Identification
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Primary system values PRIMVAL - -
19.11.2 Functionality
M15288-3 v6
The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.
19.11.3 Settings
PID-1626-SETTINGS v17
Table 625: PRIMVAL Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Frequency 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency
PhaseRotation Normal=L1L2L3
Inverse=L3L2L1
- - Normal=L1L2L3 System phase rotation
1MRK 506 382-UEN A Section 19
Basic IED functions
Line distance protection REL650 2.2 IEC 829
Technical manual