iHP Manual 110 | P a g e
iHP Owners Manual
Command
Command Name
Remarks
0x7Ah
STATUS_VOUT
ISOCOMM will read each module STATUS_VOUT reporting.
ISOCOMM will perform OR operation of STATUS_VOUT of all
modules belonging to the group.
0x7Bh
STATUS_IOUT
ISOCOMM will read each module STATUS_IOUT reporting.
ISOCOMM will perform OR operation of STATUS_IOUT of all
modules belonging to the group.
0x7Ch
STATUS_INPUT
ISOCOMM will read each module STATUS_INPUT reporting.
ISOCOMM will perform OR operation of STATUS_INPUT of all
modules belonging to the group.
0x7Dh
STATUS_TEMPERATURE
ISOCOMM will read each module STATUS_TEMPERATURE
reporting.
ISOCOMM will perform OR operation of STATUS_TEMPERATURE of
all modules belonging to the group.
0x7Eh
STATUS_CML
ISOCOMM will read each module STATUS_CML reporting.
ISOCOMM will perform OR operation of STATUS_CML of all
modules belonging to the group.
0x80h
STATUS_MFR_SPECIFIC
ISOCOMM will read each module STATUS_MFR_SPECIFIC reporting.
ISOCOMM will perform OR operation of STATUS_MFR_SPECIFIC of
all modules belonging to the group.
0x8Bh
READ_VOUT
Group configured connection - Parallel:
ISOCOMM will read each module output voltage reporting.
ISOCOMM will average the reported output voltage of the
modules in the group.
Group configured connection - Series:
ISOCOMM will read each module output voltage reporting.
ISOCOMM will sum up each reported output voltage of the
modules in the group.
0x8Bh
READ_IOUT
Modules connected in Parallel:
ISOCOMM will read each module output current reporting.
ISOCOMM will sum each reported output current of the
modules in the group.
Modules connected in Series: