VC-6000
TM
Compact monitor Part C BCU measurement
- 26 - C100583.002 Components Vers. 07 © VC-6000
TM
Compact monitor Sept. 2011
♦ <Multiplier> and <Divider>
These two parameters can be used for normalising the BCU
measurement. Both parameters are integral values that can be changed
within a setting range.
The following is valid: BCU
normalised
= BCU
non-normalised
* multiplier / divider
Setting range - multiplier:
Minimum : + 1 Maximum: + 1000 Step size: 1
Setting range - divider:
Minimum : + 1 Maximum: + 1000 Step size: 1
Advice for setting the multiplier and divider:
To guarantee a good comparative value for BCU measurements, the
measured BCU value is usually normalised through a multiplier / divider to
the value 1. In the process of measuring and monitoring only the relative
changes in the value are then interesting.
Example:
Initial measured BCU value (not normalised) = 5.
Normalise to BCU = 1 (Good condition / New condition) by a divider of 5.
After normalisation a relative change of 100 % is measured as BCU value
= 2 (instead of BCU value = 10 without normalisation).
6.2.1 Summary of the parameters
Parameter name Value range changeable
Averaging time 0.01 s...99.9 s Yes
Multiplier 1...1000 Yes
Divider 1...1000 Yes