VC-6000
TM
Compact monitor Part C DC measurement
- 28 - C100583.002 Components Vers. 07 © VC-6000
TM
Compact monitor Sept. 2011
<Zero offset>
The zero offset of the units of the DC measured value. The set value
corresponds to the measurement at an input of 0V or 0 mA.
Example:
Measured signal 4-20 mA at measurement range 0-16 eu zero offset is at
-4 eu.
The zero offset can be changed within the setting range.
Setting range of the DC zero offset:
Minimum: -9999.99 Maximum: + 9999.99 Step size: 0.01
Works pre-setting 0.000
7.2.1 Summary of the parameters
Parameter name Value range changeable
Averaging time 0.01 s...99.99 s Yes
Zero offset -9999.99...+ 9999.99 Yes