Cycle-DC measurement Part C VC-6000
TM
Compact monitor
© VC-6000
TM
Compact monitor Sept.2011 C100583.002 Components Vers. 07 - 57 -
Continuous averaging of complete trigger cycles
While continuous averaging the length L1 is equal the length L2
(L1=L2), from this arises a geomtry factor of 1.
Length L1: Distance between crosshead and
the con-rod centre position
Length L2: Distance between crosshead and piston ring
Geometry factor: Length L2 / Length L1
Read value = (measured DC voltage
) * geometry factor + zero point
Sensor sensitivity
Note:
The read value is influenced by the sign preceding the value of the sensor
sensitivity (see Sensor block).
18.2 Parameters and setting ranges
18.2.1 Parameter list
<Mode>
This parameter defines the desired operating mode of the Cycle-DC
measurement:
Mode
One position
Two positions
Averaged cycle
Works pre-
setting
One position
<No. of averages>
This parameter defines the number of trigger cycles that are averaged
for the measurement calculation.
Minimum: 1 Maximum: + 99999 Step size: 1
Works pre-
setting
50