MAX-HOLD Part C VC-6000
TM
Compact monitor
© VC-6000
TM
Compact monitor Sept.2011 C100583.002 Components Vers. 07 - 47 -
15 MAX-HOLD
15.1 Function
The MAX-HOLD measurement continuously acquires the maximum
value of the scalar value.
The maximum value is continuously overwritten by any new higher
value.
The MAX-HOLD measurement is an optional signal path component.
The MAX-hold measurement is arranged in the signal-flow chart directly
after a measurement value component.
There are a number of ways to reset the MAX-HOLD block. The reset
can be carried out locally or remotely:
(i) Over a connected Binary-input
(ii) Over the OPC-server
(iii) Through a global Reset
15.2 Parameters and setup ranges
15.2.1 Display parameters
<Max value>
Corresponds to the actual stored maximum value.
Max value
Current value
<Unit>
The unit parameter is determined by the application firmware creation
and can only be changed by a new firmware download.
Unit m/s², g, in/s², mm/s², mm/s in/s, mm,
µm, mils, eu, 1, C, F, K, V, BCU, R, s,
mA, in, rpm, Hz, cpm,