Binary-input block Part C VC-6000
TM
Compact monitor
© VC-6000
TM
Compact monitor Sept.2011 C100583.002 Components Vers. 07 - 17 -
<Delay high>
This parameter defines the time delay after a change of the signal state
from LOW (0 V) to HIGH (+24 V)
The logical change of state is completed only after the new signal state
HIGH (+24 V) has existed uninterrupted for longer than the set time
delay.
Minimum: 0.0 s Maximum: 999.99 s Step size: 0.01
Works pre-setting 0.1 s
<Delay low>
This parameter defines the time delay after a change of the signal state
from HIGH (+24 V) to LOW (0 V).
The logical change of state is completed only after the new signal state
LOW (0 V) has existed uninterrupted for longer than the set time delay.
Minimum: 0.0 s Maximum: 999.99 s Step size: 0.01
Works pre-setting 0.1 s
<Hardware ID.>
This parameter provides information about the input module type.
The settings are defined by the application firmware of the
VIBROCONTROL 6000 Compact monitor and cannot be changed at the
instrument.
Hardware ID. 11
3.2.2 Summary of the parameters
Parameter name Value range changeable
Socket no. 1, 2, 3, 4, 5, 6, 7, 8, 9 No
Channel no. A, B or C No
Active signal Yes / No Yes
Active state High / Low Yes
Delay High 0.0 s...999.99 s Yes
Delay Low 0.0 s...999.99 s Yes
Hardware Id. 11 No