VC-6000
TM
Compact monitor Part C Cyclic peak-peak measurement
- 46 - C100583.002 Components Vers. 07 © VC-6000
TM
Compact monitor Sept. 2011
♦ <Decay time>
The decay time parameter corresponds to the discharge time-constant
of the s
max
measurement. The decay time can be changed within its
setting range.
Setting range for the time-constant of the decay time:
Minimum: 0.1 s Maximum: 9.9 s Step size: 0.1 s
Works presetting 5.0 s
Advice for setting the decay time:
A longer decay time tends to smooth out fast changes in the signal
progression. The measured s
max
value will be maintained at a higher value
than with a shorter decay time. The decay time should be set at least 100
times longer than the rise time.
14.2.1 Summary of the parameters
Parameter name Value range changeable
Rise time 1 ms...99 ms Yes
Decay time 0.1 s...9.9 s Yes