COM block Part C VC-6000
TM
Compact monitor
© VC-6000
TM
Compact monitor Sept.2011 C100583.002 Components Vers. 07 - 83 -
25.2 Parameters and their setting ranges
25.2.1 Parameter list
<Instrument address / Device address>
This parameter determines the address of the
VIBROCONTROL 6000 Compact monitor in the network. Because
many VIBROCONTROL 6000 Compact monitor in a network can
communicate with a common OPC DA-server Type 7131 , each
individual VIBROCONTROL 6000 Compact monitor must be assigned a
unique instru-ment address (device address).
Instrument
address/
Device address
1 ... 247
Works pre-setting 1
Note:
The OPC DA-server Type 7131 takes over the setting of the instrument
address. This setting should not be changed !
<Baudrate>
This parameter determines the Baudrate that will be used for
communication.
Baudrate 4,800 / 9,600 /14,400 / 19,200 / 38,400 /
56,000 / 57,600 / 115,200
Works presetting 115,200
<Data format>
This parameter is preset by selection of the protocol. However this can
be changed if required due to the on-site conditions.
Data format with
Byte size/Parity/Stopbits
8 / E / 1 8/ N / 1 8 / O / 1
Works presetting 8 / N / 1
<RcvTx, TrmTx, TrmExcp, RcvBusy, RcvOvFl, RecDevErr,
RcvFrmErr, RcvCRCErr>
These parameters are exclusively for fault analysis in special cases.