EasyManuals Logo

Bosch Solution 6000-IP Installation Guide

Bosch Solution 6000-IP
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
Solution 6000-IP
Installation Manual Comms Programming
9-4
Bosch Security Systems 10/22 BLCC615I
Comms > Reporting >
Emergency Route
MENU 5-4-4
00 - Log Events Only 0 1
01 - Dest 1 + Log
02 - Dest 2 + Log
03 - Dest 1 & 2 + Log
04 - Dest 2 If 1 Fails
(*** System Wide Parameter ***)
This menu programs the destination that all Keypad
emergency alarms are reported.
1) Press [MENU] + [5] + [4] + [4]. The keypad will
display the current Emergency Route.
Emergency Route
01 - Dest 1 + Log
Press  0-9 OK to SAVE
2) Use the up and down arrow keys to select the
Keypad Emergency route required then press [OK]
to save and exit or press [MENU] to exit without
saving.
Comms > Reporting >
Swinger Dialler
MENU 5-4-5
(*** System Wide Parameter ***)
0 6
Swinger Dialler can be used to prevent a faulty or run-
a-way PIR from continually re-triggering the zone and
reporting to the base station.
The Swinger Dialler count sets the maximum number of
times an individual zone can trigger an alarm during the
current arming cycle before it is locked out.
If this option is not programmed, the panel will continue
to report the alarm signal until the system or area is
disarmed.
Only zones that have been programmed for Lockout
Dialler in MENU 3-1-7 — Report Options will follow the
Swinger Dialler count.
1) Press [MENU] + [5] + [4] + [5]. The keypad will
display the current Swinger Dialler count.
Swinger Dialler
6
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the new Swinger
Dialler count then press [OK] to save and exit or
press [MENU] to exit without saving. Valid entries
are 0 - 15 / 0 = disabled.
Comms > Reporting >
Burg Report Delay
MENU 5-4-6
(*** System Wide Parameter ***)
0 0 0
Seconds
This menu programs how long the panel will delay
reporting Burglary alarm reports. Only burglary (non-
fire) zones that have been programmed for Delay Report
in MENU 3-1-7 — Report Option will follow the Burglary
Report Delay time.
1) Press [MENU] + [5] + [4] + [6]. The keypad will
display the current burglary report delay time.
Burg Report Delay
000 Seconds
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the new report delay
time then press [OK] to save and exit or press
[MENU] to exit without saving. Valid entires are 0
to 255 seconds
Comms > Reporting >
Fire Report Delay
MENU 5-4-7
(*** System Wide Parameter ***)
0 0 0
Seconds
This menu programs how long the panel will delay
reporting fire zone alarm reports. Only fire zones that
have been programmed for Delay Report in MENU 3-1-7
— Report Option will follow the Fire Report Delay time.
1) Press [MENU] + [5] + [4] + [7]. The keypad will
display the current Fire Report Delay time.
Fire Report Delay
000 Seconds
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the new report delay
time then press [OK] to save and exit or press
[MENU] to exit without saving. Valid entires are 0
to 255 seconds.

Table of Contents

Other manuals for Bosch Solution 6000-IP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Solution 6000-IP and is the answer not in the manual?

Bosch Solution 6000-IP Specifications

General IconGeneral
Event LogYes
Areas1
Partitions1
Outputs2
CommunicationIP, GSM
Mobile AppYes
AutomationYes
System TypeHybrid
Battery BackupYes
KeypadsUp to 8

Related product manuals