Solution 6000-IP
Installation Manual System Programming
11-14
Bosch Security Systems 10/22 BLCC615I
SYSTEM OPTIONS
System > System Options >
General Options
MENU 7-7-0
1 Display LAN Fail Y
2 Report LAN Fail Y
3 Alarm On LAN Fail N
4 Cannot Change Own PIN N
5 Extend LAN Fail N
6 Monitor Default PINs Y
7 PIN Always Required N
8 Display Menu Numbers Y
(*** System Wide Parameter ***)
This menu allows you to configure the general system
options. All options are global to users, areas and keypads.
1) Press [MENU] + [7] + [7] + [0]. The keypad will
display the current general system options.
Display LAN Fail
Report LAN Fail
Alarm On LAN Fail
Press OK ON OFF MENU
2) Use the up and down arrow keys to highlight the
option then press the [ON] key to enable or the
[OFF] key to disable. Repeat Step 2 until all options
are programmed as required.
3) Press [OK] to save and exit or press [MENU] to exit
without saving.
Display LAN Fail
Setting this option allows all connected keypads to
display a system trouble when a device connected the
the system LAN has failed to communicate to the panel.
Report LAN Fail
Setting this option allows the panel to report which LAN
device has failed to the base station.
Alarm On LAN Fail
Setting this option allows the panel to sound an
alarm when a device connected to the LAN failed to
communicate to the panel.
Cannot Change Own PIN
Setting this option prevents all users the ability to
change their own PIN.
Extend LAN Fail
This option allows the control panel to support the CM430S
LAN to Ethernet modules. This option extended the time
required for the system to register a LAN module fail to
75 seconds when a keypad or module has been unable to
communicate to the control panel.
Monitor Default PINs
Setting this option will cause the panel to monitor the
default Installer PIN and User 1 PIN which are factory set
to 1234 and 2580 respectively. If either of these codes
are left as default then the keypad will display the system
trouble Default PIN. The fault will clear once the code or
codes have been changed.
PIN Always Required
Setting this option will force the system to request a
valid PIN to be entered before any menu functions can
be accessed. If this option is not set then some restricted
menu options will be available without entering a valid
PIN.
Display Menu Numbers
Setting this option causes the keypad to display
the menu numbers for all commands and menu
programming options. The menu numbers can be used
as navigation shortcuts when programming.
System > System Options >
Area Options
MENU 7-7-1
1 Area 1 Common N
2 First Open Last Close N
3 Reset Siren All Users Y
4 Power Up As Down Y
5 Fault ACK All Areas Y
6 Delay Trouble Beeps Y
7 Power Up Disarmed N
8 Ignore Trouble On Arm N
(*** System Wide Parameter ***)
This menu allows you to configure the Area system
options. All options are global to users, areas and
keypads.
1) Press [MENU] + [7] + [7] + [1]. The keypad will
display the current Area system options.
Area 1 Common
First Open Last Close
Reset Siren All Users
Press OK ON OFF MENU
2) Use the up and down arrow keys to highlight the
option then press the [ON] key to enable or the
[OFF] key to disable.
3) Repeat Step 2 until all options are programmed as
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Area 1 Common
Setting this option will cause the system to automatically
arm Area 1 All On when all other areas have been turned
on. As soon as any area is turned off the system will
automatically turn Area 1 off. Only one common area is
available on the system. If no common area is required