Solution 6000-IP
Installation Manual Programming Examples
12-2
Bosch Security Systems 10/22 BLCC615I
Auto Arming an Area using a Timezone
The control panel can be configured to automatically arm
and or disarm an area automatically if required using a
Timezone.
Procedure
1) To setup an Auto Arming time, select a timezone
that is not being used, and program the timezone
name in MENU 7-5-0 to something convenient.
2) Set the timezone period stop time in MENU 7-5-1
for the arming time you require. The START time
should be set to --:--am (by pressing the [OFF] key),
which prevents the system from auto disarming.
3) Set the timezone period day in MENU 7-5-2 for the
days of the week you require the area to
automatically arm.
4) Set the timezone that you want the area to follow
in MENU 2-1-8.
5) Set the global Auto Arm Pre Alert time (default = 10
minutes) in MENU 2-8-4.
i
Note
The auto arm pre alert time will commence when the
timezone stop time occurs. When the auto arm pre
alert time has finished, the area(s) will automatically
turn on.
Unlock a Door using a LAN Reader
This example assumes LAN Reader 9, Door Assignment 4 ,
User 1 and Output 5 are being used.
Procedure
1) Assign LAN Reader 9 to Door Assignment 4 in
MENU 6-1-7.
2) Set output 5 to Event type to 60 - Door in MENU
4-1-1 and the output Door Assignment to 4 in
MENU 4-1-2. Set the output Polarity in MENU 4-1-3
and the output Time Parameter in MENU 4-1-4 as
required.
3) Assign the user to Door 4 in MENU 1-4-5. Users can
belong to multiple doors.
4) Assign the LAN Reader Home Area to 0 (All Areas)
in MENU 6-1-3 and then disable Options 1, 2, 3 & 4
in MENU 6-1-2.
5) Program the Door Assignment for User 1 in MENU
1-4-5 as 4.
6) Add a token to User 4 in MENU 1-2-0.
7) Exit programming mode and present the token to
the LAN reader to access the door.
Unlocking a Door and Disarming Area 1 using a LAN
Reader
This example assumes LAN Reader 9, Door Assignment 4 ,
User 1 and Output 5 are being used.
Procedure
1) Assign LAN Reader 9 to Door Assignment 4 in
MENU 6-1-7.
2) Set output 5 to Event type to 60 - Door in MENU
4-1-1 and the output Door Assignment to 4 in
MENU 4-1-2. Set the output Polarity in MENU 4-1-3
and the output Time Parameter in MENU 4-1-4 as
required.
3) Assign the user to Door 4 in MENU 1-4-5. Users can
belong to multiple doors.
4) Assign the LAN Reader Home Area to 1 (Area 1) in
MENU 6-1-3 and then disable Options 1, 2 & 4 in
MENU 6-1-2.
5) Program the Door Assignment for User 1 in MENU
1-4-5 as 4.
6) Add a token to User 4 in MENU 1-2-0.
7) Exit programming mode and present the token to
the LAN reader to access the door.
Unlock a Door and Arm/Disarm Area 1 using a LAN
Reader
This example assumes LAN Reader 9, Door Assignment 4 ,
User 1 and Output 5 are being used.
Procedure
1) Assign LAN Reader 9 to Door Assignment 4 in
MENU 6-1-7.
2) Set output 5 to Event type to 60 - Door in MENU
4-1-1 and the output Door Assignment to 4 in
MENU 4-1-2. Set the output Polarity in MENU 4-1-3
and the output Time Parameter in MENU 4-1-4 as
required.
3) Assign the user to Door 4 in MENU 1-4-5. Users can
belong to multiple doors.
4) Assign the LAN Reader Home Area to 1 (Area 1) in
MENU 6-1-3 and then disable Options 2 & 4 in
MENU 6-1-2.
5) Program the Door Assignment for User 1 in MENU
1-4-5 as 4.
6) Add a token to User 4 in MENU 1-2-0.
7) Exit programming mode and present the token to
the LAN reader to access the door.

Table of Contents

Other manuals for Bosch Solution 6000-IP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Solution 6000-IP and is the answer not in the manual?

Bosch Solution 6000-IP Specifications

General IconGeneral
Event LogYes
Areas1
Partitions1
Outputs2
CommunicationIP, GSM
Mobile AppYes
AutomationYes
System TypeHybrid
Battery BackupYes
KeypadsUp to 8

Related product manuals