CG Drives & Automation,01-5326-01r5 209
Analogue Output Status [727]
Indicates the status of the analogue outputs. Fig. 147. E.g. if
4-20 mA output is used, the value 20% equals to 4 mA.
Fig. 147 Analogue output status
Communication information
The first row indicates the Analogue outputs.
1 AnOut 1
2 AnOut 2
Reading downwards from the first row to the second row the
status of the belonging output is shown in %:
-100%AnOut1 has a negative 100% output value
65%AnOut2 has a 65% output value
The example in Fig. 147 indicates that both the Analogue
outputs are active.
I/O board Status [728] - [72A]
Indicates the status for the additional I/O on option boards
1 (B1), 2 (B2) and 3 (B3).
Communication information
Area D Stat[72B]
These menus are not visible in the control panel display.
Only used in EmoSoftCom PC-tool (optional) and can be
read via fieldbus or serial communication.
Area D LSB [72B1]
Status bits 0 to 15.
see Chapter 10.2.1 page 75
Communication information
Area D MSB [72B2]
Status bits 16 and up.
see Chapter 10.2.1 page 75
Communication information
VIO Status[72C]
Shows the values of the 8 Virtual IO´s in menu[560]
Communication information
Modbus Instance no/DeviceNet no: 31023, 31024
Profibus slot/index 121/167, 121/168
EtherCAT and CANopen index (hex) 23ff, 2400
Profinet IO index 1023, 1024
Fieldbus format Long, 1=1%
Modbus format EInt
NOTE: The shown percentages are absolute values
based on the full range/scale of the in- or output; so
related to either 0–10 V or 0–20 mA.
Modbus Instance no/DeviceNet no: 31025 - 31027
Profibus slot/index 121/170 - 172
EtherCAT and CANopen index (hex) 2401 - 2403
Profinet IO index 1025 - 1027
Fieldbus format UInt,
bit 0=DigIn1
bit 1=DigIn2
bit 2=DigIn3
bit 8=Relay1
bit 9=Relay2
bit 10=Relay3
Modbus format
727 AnOut 1 2
Stp -100% 65%
728 IO B1
Stp RE 000 DI100
Modbus Instance no/DeviceNet no: 30180
Profibus slot/index 118/89
EtherCAT and CANopen index (hex) 20b4
Profinet IO index 180
Fieldbus format UInt
Modbus format UInt
Modbus Instance no/DeviceNet no: 30182
Profibus slot/index 118/91
EtherCAT and CANopen index (hex) 20b6
Profinet IO index 182
Fieldbus format UInt
Modbus format UInt
Modbus Instance no/DeviceNet no: 30181
Profibus slot/index 118/90
EtherCAT and CANopen index (hex) 20b5
Profinet IO index 181
Fieldbus format UInt
Modbus format UInt
72C VIO Status
Stp 00000000