220 Troubleshooting, Diagnoses and Maintenance CG Drives & Automation, 01-5326-01r5
Table 44 Trip condition, their possible causes and remedial action
Trip condition Possible Cause Remedy Size**
Motor I
2
t
“I
2
t”
I
2
t value is exceeded.
- Overload on the motor according to the
programmed I
2
t settings.
- Check on mechanical overload on the
motor or the machinery (bearings,
gearboxes, chains, belts, etc.)
- Change the Motor I
2
t Current setting in
menu group [230]
PTC
Motor thermistor (PTC) exceeds maximum
level.
NOTE: Only valid if option board PTC/
PT100 is used.
- Check on mechanical overload on the
motor or the machinery (bearings,
gearboxes, chains, belts, etc.)
- Check the motor cooling system.
- Self-cooled motor at low speed, too high
load.
- Set PTC, menu [234] to OFF
Motor PTC
Motor thermistor (PTC) exceeds maximum
level.
NOTE: Only valid if [237] is enabled.
- Check on mechanical overload on the
motor or the machinery (bearings,
gearboxes, chains, belts, etc.)
- Check the motor cooling system.
- Self-cooled motor at low speed, too high
load.
- Set PTC, menu [237] to OFF
002 -
105
PT100
Motor PT100 elements exceeds maximum
level.
NOTE: Only valid if option board PTC/
PT100 is used.
- Check on mechanical overload on the
motor or the machinery (bearings,
gearboxes, chains, belts, etc.)
- Check the motor cooling system.
- Self-cooled motor at low speed, too high
load.
- Set PT100 to OFF, menu [234]
Motor lost
Phase loss or too great imbalance on the
motor phases
- Check the motor voltage on all phases.
- Check for loose or poor motor cable
connections
- If all connections are OK, contact your
supplier
- Set motor lost alarm to OFF.
Locked rotor
Torque limit at motor standstill:
- Mechanical blocking of the rotor.
- Check for mechanical problems at the
motor or the machinery connected to the
motor
- Set locked rotor alarm to OFF.
Ext trip
External input (DigIn 1-8) active:
- active low function on the input.
- Check the equipment that initiates the
external input
- Check the programming of the digital
inputs DigIn 1-8
Ext Mot Temp
External input (DigIn 1-8) active:
- active low function on the input.
- Check the equipment that initiates the
external input
- Check the programming of the digital
inputs DigIn 1-8
Internal error Internal alarm Contact service
Mon MaxAlarm
Max alarm level (overload) has been
reached.
-Check the load condition of the machine
-Check the monitor setting in section 11.6.1, page
159.
Mon MinAlarm
Min alarm level (underload) has been
reached.
-Check the load condition of the machine
-Check the monitor setting in section 11.6.1, page
159.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CG Emotron VFX Series and is the answer not in the manual?

CG Emotron VFX Series Specifications

General IconGeneral
BrandCG
ModelEmotron VFX Series
CategoryController
LanguageEnglish

Related product manuals