EasyManua.ls Logo

ComAp InteliCompact NT

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
182
Setpoint: AI3 Yel
Group
Engine Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 3.
Setpoint: AI3 Red
Group
Engine Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the red alarm configured to the analog input 3.
Setpoint: AI3 Del
Group
Engine Protect
Range [units]
0 ... 180 [s]
Related
applications
All
Description
Delay of the alarms configured to the analog input 3.
Setpoint: WrnMaintenance
Group
Engine Protect
Range [units]
0 ... 10000 (OFF) [h]
Related
applications
All
Description
Adjust this setpoint to the requested next maintenance interval. The value
will count down when engine is running and if reaches zero, the alarm
Maintenance timer will appear.
This timer is also available in the value group Statistics, but it cannot be
modified there.
In the event that WrnMaintenance is set to 10000 h the timer is disabled and
not visible on the controller display.

Table of Contents

Other manuals for ComAp InteliCompact NT

Related product manuals