Event Msg enable/disable sending of event SMS
Tel No/Addr Ch1 or Tel No/Addr Ch2 field for administrator’s GSM phone number
The following events can be received by mobile phone:
- Engine Start/Stop
o Manual Start/Stop
o Remote Start/Stop
o Gen Peak Start/Stop
o PMS StartStop (as Power Management System Start/Stop)
o AMF Start/Stop (as Automatic Mains Failure Start/Stop)
o Test Start/Gen-set Stop
- Mains Fail
- Mains Returned
- Load on Mains
- Load on Genset
- Parallel Operation
- Test On Load
Message structure (e.g.):
Genset Name [hh:mm:ss dd.mm.yyyy]
hh:mm:ss Mains Fail
hh:mm:ss AMF Start
hh:mm:ss Load on Genset
hh:mm:ss Mains Returned
hh:mm:ss Parallel Oper.
hh:mm:ss Load on Mains
hh:mm:ss AMF Stop
3.20.6 InternetBridge-NT
The InternetBridge-NT (IB-NT) is a communication module that allows connection of a single controller
as well as a whole site to the internet or a Local Area Network. The internet connection can be
enabled via the built-in cellular modem supporting 2G and 3G networks or via Ethernet cable.
For InteliCompact
NT
the following functions are available:
- Direct Ethernet connection to ComAp configuration and monitoring tools (LiteEdit, InteliMonitor
or WebSupervisor)
- AirGate support
- Web interface
NOTE:
Support of InteliCompact
NT
controllers is in IB-NT 1.2 SW and newer.
For further information and options that can be set, see IB-NT Reference Guide.