InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Binary input: Load Reserve 2
This input selects the currently used pair of reserves for the power
management. If the input is active, the pair LoadResStrt 2 and LoadResStop
2 is active instead of LoadResStrt 1 and LoadResStop 1.
Binary input: Min Run Power
Use this input if you need to ensure that the nominal power of loaded gen-
sets does not drop below the value of Min Run Power even if the reserve for
stop is fulfilled.
Binary input: Top Priority
If this input is active, the controller will have the highest priority in the group
independent of the setpoint Priority. Setpoint is evaluated only in Load
Demand Star/Stop regime.
16.3.3 SPtM specific
Binary input: Rem Start/Stop
Use this input to start and stop the gen-set in AUT mode.
Binary input: Remote TEST
This input switches the controller into TEST mode independent of which
mode is selected by the mode selector on the controller main screen. Learn
more about controller modes in the Operating modes chapter.
If multiple “remote mode” inputs are active at the same time, the highest
priority is held by Remote OFF, then Remote TEST, Remote MAN and
Remote AUT.
Binary input: Rem TEST OnLd
This input switches the controller into TEST mode like Remote TEST, but
forces the controller to take the load, i.e. perform the test on load procedure.