NOTE:
Since version IC-NT 2.0 setting #RunHrsMaxDiff = 0 or 65000 no longer switch
off the function of run hours equalization.
NOTE:
There is additional 200 ms time gap after SysAMFstrtDel in order to allow the
controllers to calculate which gen-set has to start.
This setpoint adjusts the delay of the system activation after the binary input
Sys Start/Stop has been activated.
This delay is typically used as “AMF start delay”, similar to the setpoint
EmergStart Del in SPtM, on multiple AMF applications without
MainsCompact. See MINT basic schemes.
This setpoint adjusts the delay of the system deactivation after the binary
input Sys Start/Stop has been deactivated.
This delay is typically used as “Mains return delay”, similar to the setpoint
MainsReturnDel in SPtM, on multiple AMF applications without
MainsCompact. See MINT basic schemes.
-32000 ... LoadResStop 1 [#PowerMgmtMode dependent]
This setpoint adjusts the reserve for start if the set 1 of reserves is selected,
i.e. binary input Load Reserve 2 is not active. See the power management
description to learn more about reserves.