This setpoint adjusts the priority of the gen-set within the group. A lower
number represents a “higher” priority, i.e. a gen-set with lower number will
start before another one with higher number.
If the binary input Top Priority is active, the gen-set gets the highest
priority (0) independent of the setpoint setting.
NOTE:
If more than one gen-set have the same priority they will act as “one big”
gen-set.
CAUTION:
Value of the setpoint Priority is taken into account only for Load Demand
Start/Stop power management.
DISABLED, RUN HOURS, EFFICENT
This setpoint selects the method of optimization of priorities:
Optimization is disabled. Priorities are given directly by the
values adjusted in the setpoint Priority.
The priority setpoints are automatically updated
(swapped) to equalize running hours of the gen-sets or to
keep constant difference of running hours by the
controller.
This method changes the priorities (not the setpoints
itself) to optimize which gen-sets are running according to
their capacities and actual load demand. Note that this
priority swapping function may be used only if #Pwr
mgmt mode is set to ABS (kW).
Optimal power band (number of running gen-sets) is
calculated based on the nominal power of each gen-set,
their Run Hours and requested Load reserve. For gen-
sets with the same nominal power also run hour
equalization is being performed.
NOTE:
Binary input Top Priority can be used only if #PriorAutoSwap = DISABLED