250
Binary input: GCB Button
Related
applications
All
Description
This input is to be used as an external GCB button for control of the gen-set
in manual mode. It works the same way as the GCB button on the panel.
Binary input: ForwSyncDisabl
Related
applications
All
Description
If the input is active, the controller will not continue to synchronize after Min
Stab Time elapsed even in AUT mode. If an island condition occurs (mains
fails), the gen-set will take the island load.
Binary input: NeutralCB fdb
Related
applications
All
Description
Use this input to detect whether the Neutral circuit breaker is open or closed.
See also setpoint #Neutral cont and binary output Neutral CB C/O.
Binary input: PerFuelConsRes
Related
applications
All
Description
If the input is active, the controller will not continue to synchronize after Min
Stab Time even in AUT mode. If an island condition occurs (mains fails), the
gen-set will take the island load.
16.3.2 MINT specific
Binary input: Sys Start/Stop
Related
applications
MINT
Description
This input activates the power management in the controller. If this input is
not active, the gen-set is stopped in AUT mode and does not take part within
the power management of the group.
NOTE:
In most cases this input is wired parallel into all controllers within the group
to activate and deactivate the whole group. If you want to deactivate one
particular gen-set, switch it out from AUT mode.
NOTE:
If the power management is disabled by the Pwr Management setpoint, the
gen-set is started and stopped only according to this input.