InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
274
Binary output: MCB UV Coil
Related
applications
SPtM
Description
This output is to be used for control of the undervoltage coil of the mains
circuit breaker. See the chapter Circuit breakers for details about all outputs
available for generator/mains power switches.
Binary output: Ready To AMF
Related
applications
SPtM
Description
The output is closed if the gen-set is ready to start automatically and take
the load if the mains fails, i.e.:
the gen-set is not running and
the controller is in AUT mode and
no red alarm is present in the alarmlist
Binary output: Mains Healthy
Related
applications
SPtM
Description
This output is active while mains failure is not detected, i.e. the mains are
healthy.
Binary output: Mains Fail
Related
applications
SPtM
Description
This output is active while mains failure is detected.
Binary output: Mode TEST
Related
applications
All
Description
This output is active whenever the controller is in TEST mode.
16.5 Table of internal alarms
Alarm: Emergency Stop
Alarm type
Shutdown
Alarmlist
message
Emergency Stop
Alarm evaluated
All the time
Related
applications
All