InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
25
+
-
AI COM
AI
WIRING OF ANALOG INPUTS GROUNDED SENSORS
+
-
AI COM
AI
WIRING OF ANALOG INPUTS ISOLATED SENSORS
3.13.1 Tristate inputs
Analog inputs can be used also as binary or tri-state, i.e. for contact sensors without or with circuit
check. The threshold level is 750Ω. In the case of tri-state, values lower than 10Ω and values over
2400Ω are evaluated as sensor failure (short or open circuit).
+
-
AI COM
TRISTATE
1k5
P
100R
T
BINARY
WIRING OF ANALOG INPUTS USED AS BINARY OR TRI-STATE
NOTE:
The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.