16.1.9 Group: Sync/Load Ctrl
Setpoint: Speed Gov Char
This setpoint selects the characteristic of the speed governor output of the
controller. Adjust it according to the behaviour of the remote speed input of
the governor:
POSITIVE: raising the voltage on the governor remote speed input causes
engine speed to rise.
NEGATIVE: raising the voltage on the governor remote speed input causes
engine speed to go down.
SpeedGovLowLim ... SpeedGovHiLim [V]
This setpoint adjusts the initial voltage level for the speed governor output,
which is present on the output, if no speed or power regulation loop is active.
See the chapter Governor interface for details about the recommended
settings for various governor types. To make a fine adjustment, start the
gen-set in MAN mode, leave it running unloaded and then make fine
adjustment of this setpoint to achieve nominal engine speed.
Lower limit of the speed governor output. Use this setpoint to adjust the
governor output range according to your governor type.
SpeedGovLowLim … 10.00 [V]
Upper limit of the speed governor output. Use this setpoint to adjust the
governor output range according to your governor type.