EasyManua.ls Logo

ComAp InteliCompact NT

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp May 2015
198
Setpoint: BreakerOverlap
Group
AMF Settings
Range [units]
0,0 ... 300,0 [s]
Related
applications
SPtM
Description
This setpoint adjusts maximal time period the both GCB and MCB are
closed together during the interrupt-free transfer of the load from the mains
to the gen-set and vice versa.
Setpoint: ReturnFromTEST
Group
AMF Settings
Range [units]
DISABLED, ENABLED [-]
Related
applications
SPtM
Description
Adjusting of the behaviour of the controller if the gen-set is supplying the
load in TEST mode (after mains have failed) and the mains are recovered:
DISABLED: The gen-set will remain running and supplying the load until
operating mode is changed. See Manual return from test description.
ENABLED: The controller will transfer the load back to the healthy mains
and remain running unloaded. See Automatic return from test description.
Setpoint: MCB Logic
Group
AMF Settings
Range [units]
CLOSE-ON, CLOSE-OFF [-]
Related
applications
SPtM
Description
The setpoint selects behaviour of the MCB Close/Open output:
CLOSE-ON: Binary output MCB close/open is activated, when the MCB is
requested to be closed (normal, positive logic).
CLOSE-OFF: Binary output MCB close/open is activated, when the MCB is
requested to be open (inverted, negative logic).
CAUTION!
For safety reasons it is recommended to use negative logic (CLOSE-OFF).
Using positive logic could cause the mains to be disconnected accidentally
when the controller is switched off or a wire is broken.

Table of Contents

Other manuals for ComAp InteliCompact NT

Related product manuals