16 Appendix
16.1 Table of setpoints
16.1.1 Group: Process Control
Setpoint: Baseload
Group
Process Control
Range [units]
0 Nominal power [kW]
Related
applications
SPtM
Description
Required gen-set load in parallel to mains operation.
Setpoint: Base PF
Group
Process Control
Range [units]
0.7 ... 1.0 [-]
Related
applications
SPtM
Description
Required gen-set power factor when the gen-set is running parallel to the
mains.
Setpoint: AMFStartEnable
Group
Process Control
Range [units]
NO, YES [-]
Related
applications
SPtM
Description
Use this setpoint to enable or disable the AMF operation.
Setpoint: Export Limit
Group
ProcessControl
Range [units]
DISABLED, ENABLED [-]
Related
applications
SPtM
Description
Tells controller to activate protection against power export to the Mains. The
function limits gen-set requested power to hold export power lower or equal
to the setpoint Export kW.