Setpoint: Export kW
Group
ProcessControl
Range [units]
-32000 … 32000 [kW]
Related
applications
SPtM
Description
Defines max limit for export/import in case Export Limit setpoint is set to
ENABLED. A negative value means import limit, a positive value export limit,
zero means no export/import.
Setpoint: #SysLdCtrl PtM
Group
Process Control
Range [units]
BASELOAD, LDSHARING [-]
Related
applications
MINT
Description
Load control mode in parallel to mains operation of the whole group of gen-
sets.
BASELOAD: The total power of the group is controlled to constant level
given by the setpoint #SysBaseLoad. Each loaded gen-set takes equal part
(relative to their nominal power) from this requested value. The load is
regulated locally in each controller by Load control regulation loop, load-
sharing is not active. The setpoint #Sys base load is also used for
determining which gen-sets have to run or not.
LDSHARING: Gen-sets load is controlled by MainsCompact controller to
share the total load (given by the setpoint #SysBaseLoad) with other loaded
gen-sets in such a way, that all loaded gen-sets will be loaded at the same
level (relative to gen-set nominal power). Load-sharing regulation loop is
active.
NOTE:
The LOADSHARING mode shall be used in case a MainsCompact controller
is present in the system. In systems without MainsCompact the setpoint
must be in the BASELOAD position.
NOTE:
The power factor (PF) is regulated to constant level given by the setpoint
#SysPwrFactor in parallel to mains operation and does not depend on active
load control mode.
Setpoint: #SysBaseLoad
Group
Process Control
Range [units]
0 ... 4000 [kW]
Related
applications
MINT
Description
Required total load of the gen-set group in parallel to mains operation in
baseload mode (setpoint #SysLdCtrl PtM = BASELOAD).

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals