EasyManuals Logo

ComAp InteliCompact NT Reference Guide

ComAp InteliCompact NT
291 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #231 background imageLoading...
Page #231 background image
InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
231
Value: Angle
Group
Mains
Units
°
Related
applications
All
Description
The phase shift between the gen-set and the mains voltage.
Value: MaxVectorShift
Group
Mains
Units
º
Related
applications
SPtM
Description
This is the maximum measured value of the vector shift of the generator
voltage. The value is reset to 0 automatically in the moment of closing the
GCB.
16.2.4 Group: Bus
Value: Bus Freq
Group
Bus
Units
Hz
Related
applications
MINT
Description
Bus frequency taken from phase L3.
Value: Bus V L1-N
Group
Bus
Units
V
Related
applications
MINT
Description
Bus phase L1 voltage.
Value: Bus V L2-N
Group
Bus
Units
V
Related
applications
MINT
Description
Bus phase L2 voltage.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals