176
Setpoint: CrnkFail Pause
Group
Engine Params
Range [units]
5 ... 60 [s]
Related
applications
All
Description
Pause between crank attempts.
Setpoint: Crank Attempts
Group
Engine Params
Range [units]
1 ... 10 [-]
Related
applications
All
Description
Max. number of crank attempts.
NOTE:
If the last attempt is not successful, the alarm Start fail is issued.
Setpoint: Idle Time
Group
Engine Params
Range [units]
0 ... 600 [s]
Related
applications
All
Description
This setpoint determines the duration of the Idle period which begins after
the engine is started. The output Idle/Nominal remains inactive during the
idle period. This output can be used for switching the governor between idle
and nominal speed.
Setpoint: Min Stab Time
Group
Engine Params
Range [units]
1 ... Max Stab Time [s]
Related
applications
All
Description
When the gen-set has been started and the idle timer has elapsed, the
controller will wait for a period adjusted by this setpoint before closing GCB
or starting synchronizing, even if the generator voltage and frequency are
already in limits.

Table of Contents

Other manuals for ComAp InteliCompact NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliCompact NT and is the answer not in the manual?

ComAp InteliCompact NT Specifications

General IconGeneral
BrandComAp
ModelInteliCompact NT
CategoryController
LanguageEnglish

Related product manuals