InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Pause between crank attempts.
Max. number of crank attempts.
NOTE:
If the last attempt is not successful, the alarm Start fail is issued.
This setpoint determines the duration of the Idle period which begins after
the engine is started. The output Idle/Nominal remains inactive during the
idle period. This output can be used for switching the governor between idle
and nominal speed.
When the gen-set has been started and the idle timer has elapsed, the
controller will wait for a period adjusted by this setpoint before closing GCB
or starting synchronizing, even if the generator voltage and frequency are
already in limits.