InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Min Stab Time … 300 [s]
When the gen-set has been started and the idle timer has elapsed, the
generator voltage and frequency must get within limits within this period of
time, otherwise an appropriate red alarm (generator voltage and/or
frequency) is issued.
This setpoint selects whether the cooling phase is performed at idle or
nominal speed.
Duration of the gen-set is running unloaded to cool the engine down before
stop.
Under normal conditions the engine must certainly stop within this period
after the fuel solenoid has been de-energized and the stop solenoid
energized. The stop solenoid remains energized for the entire stop time
period.
NOTE:
See the chapter Cool down and stop for details about the stop procedure.