InteliCompact
NT
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
This setpoint defines starter cutoff frequency, if the engine speed is
measured from the generator frequency and the “W” terminal from the
charging alternator is connected to the pickup input. More information is
available in the Speed measurement chapter.
NOTE:
This setpoint is active only if the setpoint Gear Teeth is adjusted to zero.
Configuration dependent [Configuration dependent]
The controller will stop cranking (starter goes OFF) if the oil pressure rises
above this limit. See the description of the start procedure in a separate
chapter.
NOTE:
If an EFI engine is used, the oil pressure is read from its ECU. In the case of
a traditional engine, the analog input 1 is configured as fixed for oil pressure
measurement.
Duration of the closing of the Prestart output prior to the starter motor being
energized. Set it to zero to disable this function.
Maximum duration the starter motor is energized.