206
Setpoint: IOM AI1 Del
Group
ExtI/O Protect
Range [units]
0 ... 180 [s]
Related
applications
All
Description
Delay of the alarms configured to the analog input 1 of the extension module
IG-IOM or IGS-PTM.
Setpoint: IOM AI2 Yel
Group
ExtI/O Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 2 of the
extension module IG-IOM or IGS-PTM.
Setpoint: IOM AI2 Red
Group
ExtI/O Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the red alarm configured to the analog input 2 of the extension
module IG-IOM or IGS-PTM.
Setpoint: IOM AI2 Del
Group
ExtI/O Protect
Range [units]
0 ... 180 [s]
Related
applications
All
Description
Delay of the alarms configured to the analog input 2 of the extension module
IG-IOM or IGS-PTM.
Setpoint: IOM AI3 Yel
Group
ExtI/O Protect
Range [units]
Limits and units depend on analog input configuration
Related
applications
All
Description
Threshold for the yellow alarm configured to the analog input 3 of the
extension module IG-IOM or IGS-PTM.