285
Description
This alarm will be issued if the controller was reset during cranking of the
gen-set. If this situation occurs, the controller supposes the starting battery
is so exhausted that its voltage drops so low when starter motor is energized
that it causes controller reset.
Alarm: Low BackupBatt
Alarm type
Shutdown
Alarmlist
message
LowBackupBatt
Alarm evaluated
All the time
Related
applications
All
Description
This alarm indicates that the internal backup battery needs to be replaced.
Alarm: Low Fuel Level 1
Alarm type
Warning
Alarmlist
message
Wrn Fuel Level
Alarm evaluated
All the time
Related
applications
All
Description
This alarm indicates that the fuel level is lower than the set yellow alarm of
relevant AI (Fuel Level).
Alarm: Low Fuel Level 2
Alarm type
Breaker open & cool down
Alarmlist
message
Stp Fuel Level
Alarm evaluated
All the time
Related
applications
All
Description
This alarm indicates that the fuel level is lower than the set red alarm of
relevant AI (Fuel Level).
Alarm: High Water Temperature 1
Alarm type
Warning
Alarmlist
message
Wrn Water Temp
Alarm evaluated
All the time
Related
applications
All
Description
This alarm indicates that the water temperature is higher than the set yellow
alarm of relevant AI (Water Temp).