Starting RPM
reached?
Another “engine
running” symptom
present?
Starter
deactivated
MaxCrank time
elapsed?
Starter activated
Engine is started
Yes
Yes
Yes
No
No
No
Starter
deactivated
Poil > Starting Poil or
Ugen > 25 Unom in at least one
phase or
D+ input activated
Starting RPM
reached?
MaxCrank time
elapsed?
Yes
No
Engine is started
RPM Meas Fail alarm
Yes
Fuel solenoid = DIESEL
Fuel solenoid
activated
500ms
delay
Fuel solenoid
deactivated
Start fail alarm
Last attempt?
Yes
Start pause
No