InteliDrive DCU Industrial 3.4.0 Global Guide
132
Setpoint group Engine protect Related FW 3.4.0
Range [units] 0 .. 65535 [h]
Default value 65535
Force value
Alternative config
Step 1
Comm object 9648 Related applications AS, SS
Description
Running hours count down counter is decremented when engine is running. Service alarm is indicated in
Alarm list and History record is done when counter reaches zero. Service time setpoint is initial counter
value and it is gradually decrement when engine runs.
Note: Once the service time has elapsed the Service time will have to be adjusted to non-zero value to
clear the alarm and begin a new countdown.
Service Time
6 back to List of setpoints
Setpoint group Engine protect Related FW 3.4.0
Range [units] [DEFAULT, ALARM ONLY]
Default value DEFAULT
Force value
Alternative config
Step [-]
Comm object 15813 Related applications AS, SS
Description
DEFAULT: COMMON WRN (PAGE 194) is activated , if ECU alarm is received by controller.
ALARM ONLY: COMMON WRN (PAGE 194) is not activated, if ECU alarm is received by controller.
ECUAlarmMode
6 back to List of setpoints