InteliDrive DCU Industrial 3.4.0 Global Guide
194
Related FW 3.4.0 Related applications AS, SS
Comm object 256
Description
The output closes if any Wrn, Sd, Cd, Fls, alarm is active and stays closed until all alarms disappear and
Fault reset is pressed = output is opened when Alarm list is empty.
Common Alarm
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 3
Description
The output closes when any Warning alarm is active. Output opens when all Wrn alarms disappear and Fault
reset is pressed (no Wrn alarm in Alarm list).
Common Wrn
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 4
Description
The output closes when any Shut-down alarm is active. Output opens when all Sd alarms disappear and
Fault reset is pressed (no Sd alarm in Alarm list).
Common Sd
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 257
Description
The output closes when any Cool-down alarm is active. Output opens when all Cd alarms disappear and
Fault reset is pressed (no Cd alarm in Alarm list).
Common Cd
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 6
Description
The output closes when any Sensor fail alarm is active. Output opens when all Fls alarms disappear and
Fault reset is pressed (no Fls alarm in Alarm list).
Common Fls
6 back to List of LBO