InteliDrive DCU Industrial 3.4.0 Global Guide
193
Related FW 3.4.0 Related applications AS, SS
Comm object 1842
Description
Indicates that Aftertreatment control is available with configured engine support.
Aftertreatment
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 1831
Description
Active signal indicates that DPF (Diesel Particulate Filter) is starting to overfill with soot because the
system is unable to undertake an automatic active regeneration. It starts flashing when the DPF is nearly
full, engine power may be reduced.
DPF Lamp
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 1373
Description
Indicates High Exhaust System Temperature (HEST). It may be active during DPF regeneration to indicate
higher than normal exhaust temperatures.
HESTīLamp
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 1
Description
Binary output for Horn, Buzzer alarm acoustic indication. Output is automatically switched off after Horn
Timeout (page 124). Horn is active unlimited time (until Fault reset) when Horn timeout = 0.
Horn
6 back to List of LBO
Related FW 3.4.0 Related applications AS, SS
Comm object 2
Description
The output closes if any alarm is activated and opens after Fault reset even if the Alarm is still active.
Alarm
6 back to List of LBO