InteliDrive DCU Industrial 3.4.0 Global Guide
176
Related FW 3.4.0 Related applications AS, SS
Comm object 46
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Starting RPM (page 115) or
Analog input Oil pressure > Starting POil (page 116) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication1
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 47
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Starting RPM (page 115) or
Analog input Oil pressure > Starting POil (page 116) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication2
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 48
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state = RPM > Starting RPM (page 115) or
Analog input Oil pressure > Starting POil (page 116) or
Active Binary input RunIndication1 or
Active Binary input RunIndication2 or
Active Binary input RunIndication3.
RunIndication3
6 back to List of LBI