Related FW 3.4.0 Related applications AS, SS
Comm object 41
Description
Skips Idle Time and switch controller from Idle to Running state when closed before Idle Time is over.
Nominal Speed
6 back to List of LBI
Related FW 3.4.0 Related applications SS
Comm object 162
Description
Binary input function for loaded engine indication.
Loaded
6 back to List of LBI
Related FW 3.4.0 Related applications AS
Comm object 163
Description
Binary input activates Engine start via clutch. Engine is started by the other running engine via closed clutch
- binary output Clutch Connect. See MaxClStrtPer (page 141) protection setpoint.
EnClutchStart
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 44
Description
Blocks all protections except Overspeed (page 129), Emergency Stop and protections configured as “Sd
override” (=Sprinkler).
All alarms are detected
Alarms are recorded on the controller Alarm list screen
Alarm are recorded into History
Enabled Active calls remains active
Controller front panel engine RED LED blinks or lights
Note: The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout Start.
Sd Override
6 back to List of LBI