InteliDrive DCU Industrial 3.4.0 Global Guide
333
BINARY OUTPUT 8 binary output
CAN CAN1 line
RS232-TTL Interface for programming
POWER Power supply
BINARY INPUTS 8 LEDs for binary input indication
BINARY OUTPUT 8 LEDs for binary output indication
Tx, Rx Indication transmitted or received data
POWER Power supply LED indication
CAN_R Terminating CAN resistor
RUI Analog inputs configuration
RESET Programming / reset
BOOT Programming
IGS Controller type selection
AIN BLOCK Block of all Analog inputs
STOP Service jumper
ADR1
Module’s address settings
ADR2
Compensation button Long wires resistance compensation
Note: Configuration jumpers IGS, ADR1, ADR2 are OPEN by default.
CAN_R jumper is CLOSE by default (IG-IOM mode).
Analog inputs are configured for resistance measurement by default.
Address and jumpers setting
Controller type selection
The type of controller to be used with IGS-PTM must be selected via jumper labeled IGS accessible at the lower
PCB.
IGS jumper Controller type
OPEN IL-NT, IC-NT, ID (FLX)
CLOSE IG-NT, IS-NT, IM-NT, ID-DCU, ID-Mobile, IL
Table 8.10 IGS jumper description
Address configuration
If IGS-NT controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labeled ADR1 and ADR2.
ADR1 ADR2 BIN module BOUT module AOUT module AIN module
Open Open 1 1 1 1
Close Open 2 2 2 2
Open Close 3 3 3 3
Close Close 4 4 4 4