Table 8.11 CAN address settings
Analog inputs hardware configuration
Analog inputs can be configured for:
Resistance measurement
Current measurement
Voltage measurement
The type of analog inputs is configured via jumpers RUI located on lower PCB.
RUI Analog input configuration
1 - 2 Resistance measuring
2 - 3 Current measuring
NO jumper Voltage measuring
Table 8.12 Analog input settings
Programming firmware
Firmware upgrade is via AT-link (TTL). For programming is necessary to close jumper BOOT. RESET jumper is
used to reset the device. Close jumper to reset the device. For programming is used FlashProg PC tool.
LED indication
Binary inputs
Each binary input has LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Binary output LED shining when binary output is set.
Power
LED status Description
Dark No required power connected
One flash and pause Compensation fail
Three flashes and
pause
Compensation successful
Flashing there is no communication between IGS-PTM and the controller.
Fast flashing Detection of CAN communication speed
Lights
Power supply is in the range and communication between IGS-PTM and controller
properly works.