InteliDrive DCU Industrial 3.4.0 Global Guide
335
Wiring
Analog inputs connection
Image 8.6 Two wire resistor sensor
Image 8.7 Two wire current sensor.
Image 8.8 Three wire current sensor.
Image 8.9 Extension of voltage measuring range.
Note: It is not necessary to connect analog inputs COM terminal to negative power supply.
Long wires resistance compensation
Process of compensation:
1. Short all wires to analog sensors at the end (replace sensors with shorting links).
2. Hold the compensation button on IGS-PTM through the hole in upper cover when switching IGS-PTM on.
3. Result of compensation will be shown in 2 seconds by flashing of POWER LED.
One flash and pause – compensation fail.
Three flashes and pause – compensation success.
4. Measured lead’s resistance is stored in EEPROM memory (separate value for each input) and is subtracted
from measured value when resistance measuring.