Figure 4-131 DC-DC Connectors (Potted)
6. IftheDC-DCConverteristhepottedstyle,removetheJ7connectorfromtheSoftStart.RefertoFigure
4-132Closed-TopSoftStartJ1andJ7Removalforthisandthefollowingstep.
NOTE
TT/TGcompressorsutilizingtheopenframeDC-DCdesigndonotutilizetheClosed-TopSoftStartJ7:TriggerSignalconnector.
7. RemovetheSoftStartAC/DCHarnessfromtheSoftstart.
a. ForcompressorswiththeClosed-TopSoftStart,removetheJ1andJ7(ifequipped)connector.
RefertoFigure4-132Closed-TopSoftStartJ1andJ7Removal.
b. ForcompressorswiththeOpen-TopSoftStart,removeconnectorsJ1andJ8.RefertoFigure4-133
Open-TopSoftStartJ1andJ8Removalonpage136.
Figure 4-132 Closed-Top Soft Start J1 and J7 Removal
M-SV-001-EN Rev. H-1/23/2023 Page 135 of 294