Compressor Status
Description
Trigger Method Troubleshooting
Verificationonpage73.
l
Verifythesolenoidactuators.RefertoSection4.6.3SolenoidVerificationonpage73.
l
VerifytheSerialDriver.RefertoSection4.26.3SerialDriverVerificationonpage217.
l
ReviewthefaultlogforactualInvertertemperatureandotherconditionsthatare
recordedatthetimeoffault.
l
TheInverterrequiresreplacementiftheembeddedtemperaturesensorisdetermined
faulty.
HighDischarge
TemperatureFault
AFT
l
Suggestsinsufficientcharge(i.e.,lowgas),thecondensertemperaturehasincreased,
checkvalvehasfailedtoopenorthecompressorhasbeenrunninginsurgecondition
foranextendedperiodoftime.
l
Checkthechillergascharge,enteringcondenserair/waterconditionsandoperational
settings.
l
Verifycheckvalveopensduringcompressoroperation.
l
Verifythedischargepressure/temperaturesensor.RefertoSection4.32.3
Pressure/TemperatureSensorVerificationonpage246.
l
Reviewthefaultlogforactualdischargetemperatureandotherconditionsthatare
recordedatthetimeoffault.
LowSuctionPressure
Fault
DFT
l
Suggestsinsufficientcharge,insufficientsystemload,orasuddendropinevaporator
enteringair/watertemperatureorflow.
l
Checkthecharge,systemloadandenteringair/waterconditions.
l
Reviewthefaultlogforactualsuctionpressureandotherconditionsthatarerecordedat
thetimeoffault.
HighDischarge
PressureFault
AFT Consequence:
l
ResultsinanInstantaneousLock-OutFault-pre-CC4.0.0
Recommendation:
l
Suggeststhecondensermaybefaultyorinsufficientair/waterflow.
l
Checkthecondenserandair/waterflow.
l
Reviewthefaultlogforactualdischargepressureandotherconditionsthatarerecorded
atthetimeoffault.
3-PhaseOver-Current
Fault
AFT Consequence:
l
Duringstartupmode,allalarmsareignoredbythecontrolsystem,butfaultsarenot.
Therefore,whentheFLAcurrent(3-PhaseAlarmLimit)isreached,thecompressorwill
continuetoaccelerateifstartuprequirementsarenotsatisfied.AfterStartupis
complete,alarmswillslowthecompressorspeed.ResultsinanInstantaneousLockOut
Fault-pre-CC4.0.0.
Requiresapowercycletoreset.
l
Indicatesthecompressorisdrawingcurrentgreaterthanthe3-PhaseCurrentFault
Limit.
Recommendation:
l
Reviewthefaultlogforrecorded3-PhaseCurrentlevel,demand,enteringair/water
temperature(ifavailable)andotherconditionsthatarerecordedatthetimeoffault.
l
Usualcausesarestartspeedsettoohigh,minimumpressureratiosettoohighatstart-
up,powercontrolintegral(loop)gainsettoohigh.Canalsoberelatedtosudden
increaseinload/demandorsystemchanges.
HighCavity
TemperatureFault
AFT Consequence
l
Indicatesthemotorcoolingisinsufficient.
CAUTION:RepeatedoccurrencesofthisfaultcanresultinshaftdemagnetizationorBackEMFislow
Page 256 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals