Compressor Status
Description
Trigger Method Troubleshooting
l
Ensuretheliquidmotor-coolinglinehassufficientliquidsupplyandisnotblocked.
l
Preventprolongedoperationatapressureratiolessthan1.5.
l
Verifythesolenoidsareoperationalandnotblocked.RefertoSection4.6.3Solenoid
Verificationonpage73.
l
Verifythesolenoidactuators.RefertoSection4.6.3SolenoidVerificationonpage73.
l
VerifytheSerialDriver.RefertoSection4.26.3SerialDriverVerificationonpage217.
l
VerifySCRtemperaturesensor.RefertoSection4.18.2.5SCRTemperatureSensor
Verificationonpage144.
l
VerifySCRs.RefertoSection4.18.2SCRVerificationonpage142.
(AlarmandFaultremovedfromCC4.2.Xandlatersoftware)
LockOutFault INS InstantaneousLockOutFault:
l
DischargePressurePre-CC4.0.0
l
3-PhaseOvercurrentPre-CC4.0.0
l
InverterErrorCC4.X.X
Ifany(oracombinationof)thefaultslistedbelowoccursmorethanthree(3)timeswithin30minutes,
aLock-Outfaultwilloccur:
l
DischargePressureCC4.X.X
l
InverterTemperature
l
SCRTemperature
l
3-PhaseOvercurrentCC4.X.X
l
MotorHighCurrent
l
InverterErrorPre-CC4.0.0
l
RotorStartingTorque
l
LowMotorBackEMF
l
Reviewfaultlogforindicationoffaultsrecordedattimeoflockoutfault.Determine
causeofthefaultsandrepairasnecessary.
l
CyclepowertoclearLock-OutFault.Activealarm/FaultViewerinSMTallowstheLock
Outcountertobemonitored.
HighWinding
TemperatureFault
AFT
l
IndicatestheRawMotorThermalReadoutintheCompressorMonitorToolhasexceeded
themaximumlimit.
l
Ensuretheliquidmotor-coolinglinehassufficientliquidsupplyandisnotblocked.
l
Preventprolongedoperationatapressureratiolessthan1.5.
l
Verifythesolenoidsareoperationalandnotblocked.RefertoSection4.6Solenoidsand
Coilsonpage72.
l
Verifythesolenoidactuators.RefertoSection4.6.3SolenoidVerificationonpage73.
l
VerifytheSerialDriver.RefertoSection4.26.3SerialDriverVerificationonpage217.
l
Verifythemotorthermistor.RefertoSection4.23.4.3StatorThermistorResistance
Verificationonpage195.
HighSuction
SuperheatFault
AFT
l
SuctionSuperheatiscalculatedfromthecompressorsuctionpressureandtemperature
values.
l
Suggestshighevaporatortemperaturecombinedwithlowevaporatorpressure,
insufficientrefrigerantcharge,checkvalvehasfailedtoopenorthecompressorhas
beenrunninginsurgeconditionforanextendedperiodoftime.
l
Checkthecharge,systemloadandenteringair/waterconditions.
l
Verifycheckvalveopensduringcompressoroperation.
Page 258 of 294 - M-SV-001-EN Rev. H 1/23/2023

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals