EasyManuals Logo
Home>Danfoss>Air Compressor>Turbocor TT Series

Danfoss Turbocor TT Series User Manual

Danfoss Turbocor TT Series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #259 background imageLoading...
Page #259 background image
Compressor Status
Description
Trigger Method Troubleshooting
l
Reviewthefaultlogforactualsuctionpressureandtemperature,enteringair/water
temperature(ifavailable)andotherconditionsthatarerecordedatthetimeoffault.
l
Verifysuctionpressure/temperaturesensor.RefertoSection4.32.3
Pressure/TemperatureSensorVerificationonpage246.
Table 5-7 Compressor Status 2 Faults
Compressor Status 2
Description
Trigger
Method
Troubleshooting
SuctionPressure
SensorFault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor
l
Verifytheassociatedsensorandrelatedconnections
Discharge
PressureSensor
Fault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor
l
Verifytheassociatedsensorandrelatedconnections
Suction
Temperature
SensorFault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor
l
Verifytheassociatedsensorandrelatedconnections
Discharge
Temperature
SensorFault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor
l
Verifytheassociatedsensorandrelatedconnections
Inverter
Temperature
SensorFault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor
l
Verifytheassociatedsensorandrelatedconnections
Cavity
Temperature
SensorFault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor.
l
Verifytheassociatedsensorandrelatedconnections
SoftStart
Temperature
SensorFault
RFT
l
Sensorerrorsoccurwhenthesensorisprovidingareadingthatisoutsidethenormalreadable
temperaturerangeandthereforemusthaveanerrorinthereadingorfunctionalproblemwiththe
sensor.
l
Verifytheassociatedsensorandrelatedconnections
InvalidBearing
CalibrationFault
INS
l
IfabearingcalibrationisnotsavedintheEEPROM,thisfaultwillbetriggered,avalidcalibrationis
requiredpriortothecompressoracceptingdemand.
l
CalibratethecompressorbearingsusingtheCalibrationToolandsavetoEEPROM.Cyclepowerand
verifythecalibrationisretainedinEEPROM.
InverterCooling
ControlFault
AFT
l
RefertoTable5-6CompressorStatusonpage255regardingHighInverterTemperatureFault
Troubleshooting
MotorCooling
ControlFault
AFT
l
RefertoTable5-6CompressorStatusonpage255regardingHighCavityTemperatureFault
Troubleshooting
M-SV-001-EN Rev. H-1/23/2023 Page 259 of 294

Table of Contents

Other manuals for Danfoss Turbocor TT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TT Series and is the answer not in the manual?

Danfoss Turbocor TT Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TT Series
CategoryAir Compressor
LanguageEnglish

Related product manuals