The relevant alarm set point is chosen in parameters 4610-4660 and 4680-4730. Each alarm can be config-
ured in two alarm levels for each differential measurement between analogue input A and input B. The figure
below shows the two parameters to configure alarm level 1 and 2, for differential measurement 1.
6.36 Sleep mode
6.36.1 Sleep mode
The sleep mode is a standstill power-saving mode. If the engine is stopped and nothing has happened within
the time setting, the unit will enter sleep mode, meaning that the most power consuming functions (for exam-
ple display) are turned off. As soon as an event occurs, the sleep mode is ended. An event could be one of
the following:
● A button is pressed on the unit or on an AOP
● Auto start/stop signal is sent, also as a Modbus command